QS-042Battery communication & BMSNo charge/discharge
Check BYD's Compatible Inverter List and inverter config, app config and firmware, terminal resistor position and PIN.
QS-043Battery communication & BMSEC111 / EC112
EC111 is normal right after start; if it stays, check inverter comms or re-save the configuration.
QS-044Battery communication & BMSEC103
Check the DIP switch (BCU1) or terminal resistor (BCU2), then restart in the defined order.
QS-045Battery communication & BMSUnexpected shutdown
It shuts down within 30 min if inverter communication is lost. Check comms and collect logs for service.
QS-054Battery start-up, charging & protectionNo LED
Check the minimum module count (HVS 2, HVM 3), then do BYD's defined off/wait/on sequence.
QS-056Battery start-up, charging & protectionEC203–EC803
The first digit shows the module position; check its connections and use the module exclusion method.
QS-057Battery start-up, charging & protectionEC110 Low voltage
Shut it down to stop further discharge, see if the inverter can force-charge, measure voltage and contact BYD service.
QS-058Battery start-up, charging & protectionSOC jumps
No. New modules ship at about 30% and SOC calibrates over full charge/discharge cycles.
QS-085Monitoring, Wi-Fi & firmwareWi-Fi not visible
The Wi-Fi switches off 5 h after start: press the LED button about 1 s to wake it, or 3x within 6 s to reset it.
QS-086Monitoring, Wi-Fi & firmwareUpdate stuck
It needs inverter comms and takes about 20 min; if it doesn't finish, rerun it and do the defined restart order.