QS-165 · Overtemperature, fans & hardware faults

My Kostal Plenticore G3 (17.5 kWp, 18 months old) is lit red with events 1106, 1013 and 1060 and takes no power from the roof. A restart didn't help. In July it showed 1016 and a restart fixed it. What do the codes mean?

The short answer
Kostal lists 1060 and 1106 as 'HW-Defekt' (hardware defect): contact support. That is a replacement case. 1013 means negative voltage at PV input 2 and 1016 means reversed or swapped strings. Both are installation faults, so have the strings checked before the new unit goes in.

Plain explanation

Kostal's event code list for the PLENTICORE G3 lists 1060 and 1106 as system faults with the description 'HW-Defekt' (hardware defect). The action for both is 'Support kontaktieren' (contact support). The red LED is on for 1060 and off for 1106. A restart doesn't clear a hardware defect, so the installer opening a replacement case through Kostal is the right step. The other two codes point to the DC side. 1013 is an installation fault: 'negative voltage at PV generator 2', meaning input 2 sees reversed voltage. 1016, seen in July, means the strings are reverse-polarised and/or swapped between inputs. The action for both is to check the PV array installation and design. Kostal also says to contact support if an event repeats or stays. Kostal's list doesn't say whether the DC faults and the hardware defect are linked, and we don't claim they are. But a repeated polarity or swapped-string event on the same system is worth ruling out. Before the replacement unit is connected, have the installer check each string's polarity and open-circuit voltage at the inverter end and confirm each string lands on its own input. Then the new unit won't start with the same DC fault.

Steps from the source

  1. Note all event codes and times from the inverter's web interface or app for the support case
  2. Installer opens a support/replacement case with Kostal for 1060 / 1106 (HW-Defekt)
  3. Before the new unit goes in: with DC isolated, the installer checks polarity and open-circuit voltage of each string and that no strings are swapped between inputs (1013 / 1016)
  4. After the swap, watch for 1013 / 1016 again; if they return, the fault is on the PV side
"Strings verpolt und/oder untereinander vertauscht."

Word for word from the source.

Source

KOSTAL Solar Electric, PLENTICORE G3 event list (Ereigniscodes, de-DE), Ereigniscodes table, rows 1013, 1016, 1060, 1106 and footnote. English PDF: https://www.kostal-solar-electric.com/fileadmin/downloadcenter/kse/Eventlist/G3/Eventlist-G3_en.pdf (curl blocked with 403; German HTML read via web fetch and saved). checked 2026-11-16 (Vilnius)documents.kostal.com ↗