PV gives 1–2 kW, the house uses about 0.5 kW and the battery is charging, yet the app shows about 100 W coming from the grid at the same time. Why, and can I stop it?

The short answer
A small, steady import is normal. Battery systems regulate to a small target at the grid point and react with a short delay, so they lean towards a little import rather than accidental export.

Plain explanation

A hybrid or battery inverter does not control power exactly at 0 W. It measures the grid point and keeps adjusting towards a target value. Victron's ESS manual explains why that target is usually slightly positive. The default grid setpoint is 50 W. A system aiming at exactly 0 W tends to overshoot into export when a big load switches off before it can react, so a small positive setpoint keeps it drawing slightly from the grid instead. Other makers expose similar settings. Huawei's LUNA2000 manual has a 'maximum grid power during battery discharge' value: with 50 W set and a 40 W load, the 40 W comes from the grid and the battery does not discharge. So 50–100 W of import while the battery charges is usually the controller's target plus meter and reaction lag, not a fault. Whether your system lets you change this, and what its default is, depends on the brand. We did not find this value in Alpha ESS's own documents, so ask your installer or Alpha ESS support. A setpoint at or below 0 W means more small exports.

Steps from the source

  1. Compare the app's grid figure with the utility meter over a full day: tens of watt-hours, not kilowatt-hours, is normal
  2. Check the system menu for a grid setpoint / grid power target or a minimum grid import setting
  3. If you change it, expect the opposite effect: more small exports when loads switch off
  4. If import is much higher (hundreds of watts constantly), have the meter/CT position and direction checked
"A system regulating to exactly 0 W will tend to overshoot into export when a large load switches off before the system can react; a small positive setpoint keeps the flow drawing slightly from the grid instead."

Word for word from the source.

Source

Victron Energy ESS Design and Installation Manual (VE.Bus), section 5.12 'Grid setpoint', Section 5.12 Grid setpoint; also Huawei LUNA2000-S1 User Manual Issue 06 (2025-09-30), ESS parameter table 'Maximum grid power during battery discharge' (p. 93), https://solar-distribution.baywa-re.de/out/media/15-LUNA2000-S1_LUNA2000-S1_User_Manual.pdf. checked 2026-11-09 (Vilnius)www.victronenergy.com ↗