The short answer
Not always. Solplanet's inverter has an internal all-pole sensitive RCMU (DIN VDE 0100-712), so an external RCD is only needed where local rules require it.
Plain explanation
Solplanet's manual says the inverter has an all-pole sensitive residual current monitoring unit that meets DIN VDE 0100-712 (IEC 60364-7-712) and is tested to IEC 62109-2, so an external RCD is not required. If local regulations require one, a type A or type B RCD can be added. Other brands say similar things, but always check the manual and your national wiring rules.
Steps from the source
- Check national wiring rules and the grid operator's terms
- Check the inverter manual for its RCMU and the allowed RCD type
- If you fit one, use the rating the manual gives
"Therefore an external residual current device (RCD) is not required."
Word for word from the source.
Source
Solplanet installation manual ASW6000–10000-S(-A), 5.4.4 Residual current protectiondownloads.osw.energy ↗