The 30 mA RCD trips on sunny mornings. Is the inverter faulty?

The short answer
Often not. A 30 mA RCD may trip at only 15 mA, and SolarEdge recommends a 100 or 300 mA type A RCD unless local code needs lower.

Plain explanation

PV systems have normal discharge current to earth, and SolarEdge warns this can nuisance-trip an external RCD with a low setting. Under IEC 61008 a 30 mA RCD may already trip at 15 mA. Where the code allows, SolarEdge recommends a type A RCD of 100 or 300 mA. Where the code demands 30 mA, pick a good-quality RCD and set the inverter's internal residual-current trip lower than the external one, because the internal one resets by itself.

Steps from the source

  1. Check the inverter manual's RCD rating before blaming the inverter
  2. Follow the local electric code first
  3. If 30 mA is mandatory: quality RCD, and set the inverter's internal trip below it
"An RCD with a rating of 30 mA may actually trip at a leakage as low as 15 mA (according to IEC 61008)."

Word for word from the source.

Source

SolarEdge Installation Guide, Single Phase Inverter with Compact Technology, Europe & APAC v1.2 (MAN-01-00488-1.2), p.28, Selecting a Residual Current Device (RCD)knowledge-center.solaredge.com ↗

Where installers ask this

General guidance based on the manufacturer's manual or the named source. Always follow the current manual for your exact model and your national code. DC and AC electrical work is for qualified installers only. Not affiliated with or endorsed by any brand named; trademarks belong to their owners.