Plain explanation
PV systems have normal discharge current to earth, and SolarEdge warns this can nuisance-trip an external RCD with a low setting. Under IEC 61008 a 30 mA RCD may already trip at 15 mA. Where the code allows, SolarEdge recommends a type A RCD of 100 or 300 mA. Where the code demands 30 mA, pick a good-quality RCD and set the inverter's internal residual-current trip lower than the external one, because the internal one resets by itself.
Steps from the source
- Check the inverter manual's RCD rating before blaming the inverter
- Follow the local electric code first
- If 30 mA is mandatory: quality RCD, and set the inverter's internal trip below it
"An RCD with a rating of 30 mA may actually trip at a leakage as low as 15 mA (according to IEC 61008)."
Word for word from the source.