At handover, the measured open-circuit voltage of all three strings is about 16% below the calculated value. Modules: LONGi Hi-MO S10 LR7-54HJBB 490 W, Voc 41.25 V (STC), −0.210%/°C. It was a very overcast, rainy day at about 5 °C. The installer says the deviation is completely normal. Is it?
Most likely yes, if all strings are low by the same amount per module. The datasheet's 41.25 V applies at 1000 W/m² and 25 °C. On a dark day the irradiance is far lower, and Voc falls with it. Your three strings agree to within about 0.2 V per module, which points to the weather, not a missing module.