How many strings can I put in parallel without string fuses?

The short answer
JinkoSolar's formula is N ≤ fuse rating / Isc + 1. For the JKM440N-54HL4R-B (25 A fuse, 13.80 A Isc) that gives 2.8, so 2 strings.

Plain explanation

When strings are in parallel, a shaded or faulty string can take reverse current from the others. JinkoSolar's installation manual gives the maximum recommended number of parallel connections as N ≤ (fuse rating / Isc) + 1, using the maximum series fuse rating and the short-circuit current from the label or datasheet. For the JKM440N-54HL4R-B: 25 A / 13.80 A + 1 = 2.81, so at most 2 strings in parallel before string fuse protection is needed. The bypass diode is not over-current protection. Local electrical codes and the inverter manual still apply.

Steps from the source

  1. Take the maximum series fuse rating and Isc from the datasheet
  2. N ≤ fuse rating / Isc + 1, round down
  3. Above that, fit string fuses sized per the module and local code
"the maximum recommended number of parallel connections is: N ≤ Fuse Rating / Isc + 1"

Word for word from the source.

Source

JinkoSolar Global Installation Manual 202605 A1.8-EN, Section 5 electrical installation, parallel-connection formula, PDF p. 24; values from JinkoSolar JKM420-440N-54HL4R-B datasheet (F1.3-EN) p. 2 (Maximum series fuse rating 25 A; Isc 13.80 A STC)jinkosolarcdn.shwebspace.com ↗

Where installers ask this

General guidance based on the manufacturer's manual or the named source. Always follow the current manual for your exact model and your national code. DC and AC electrical work is for qualified installers only. Not affiliated with or endorsed by any brand named; trademarks belong to their owners.

Get new answers and videos

We only use your email for these updates. We never sell it or give it to others for their own use. Details in our privacy notice.